NSPIRE smoke and carbon monoxide alarm requirements for Section 8 landlords
NSPIRE smoke alarm requirements call for a working smoke alarm on each level of a Housing Choice Voucher (Section 8) unit, inside each bedroom, and within 21 feet of any bedroom door measured along the path of travel. Since December 29, 2024, each must be hardwired or a sealed 10-year battery unit, and hardwired in a unit built or substantially rehabilitated after December 29, 2022.
Where the unit has a fuel-burning appliance or fireplace, or an attached garage (under NSPIRE, one without ventilation), among other cases, you also need a carbon monoxide (CO) alarm inside or right outside each bedroom. On HUD’s checklist for voucher units, dated May 8, 2026, a missing, obstructed or silent alarm of either kind is life-threatening: the unit fails, and you have 24 hours to fix it.
These placement and type rules apply now, whether your housing authority (PHA), the local agency running the voucher program, uses the old Housing Quality Standards (HQS) or NSPIRE. The Section 8 inspection checklist covers the rest of the unit.
Smoke and CO alarm rules at a glance
| Rule | Smoke alarms | CO alarms |
|---|---|---|
| Which units | Every unit | Units with a fuel-burning appliance or fireplace, an attached garage (under NSPIRE, one without ventilation), or another case below |
| Where in the unit | Each level, inside each bedroom, within 21 feet of each bedroom door measured along the path of travel, and on the living-area side of a door between an alarm outside a bedroom and the living area | Inside or right outside each bedroom, or inside each bedroom in one case; other spots allowed in two cases below |
| Common areas serving the unit | At least one on each level, and federal law adds one in each common area | Allowed in some buildings with a fuel-burning appliance: between it and the unit, or on the ceiling of its room |
| Type | Hardwired, or sealed with a 10-year battery; hardwired if built or substantially rehabilitated after December 29, 2022 | No power source set in HUD’s standard; installed to meet or exceed chapters 9 and 11 of the 2018 International Fire Code |
| No test button | Inspector asks for a smoke alarm maintenance certificate | Test item not cited |
| Missing, obstructed or silent | Life-threatening, 24 hours | Life-threatening, 24 hours |
Where do smoke alarms go in a Section 8 unit?
24 CFR 5.703(d)(3), which calls them smoke detectors, requires at least one “in proper working condition” in each of these places:
- “On each level of the unit”
- “Inside each bedroom”
- “Within 21 feet of any door to a bedroom measured along a path of travel”
- “Where a smoke detector installed outside a bedroom is separated from an adjacent living area by a door, a smoke detector must also be installed on the living area side of the door.”
One hallway alarm right next to several bedrooms counts as the alarm outside them, and can be that level’s alarm too. Basements count as a level; crawl spaces and unfinished attics do not (42 U.S.C. 1437f(o)(22)). Shared areas serving your unit need one on each level of the property, and federal law adds one in each common area.
If anyone in the unit is hearing-impaired, “the smoke detectors must have an alarm system designed for hearing-impaired persons” (24 CFR 5.703(d)(3)(ii)).
Mounting. HUD’s Smoke Alarm standard says a ceiling alarm “must be greater than 4 inches from the wall”, a wall alarm’s top edge “cannot be closer than 4 inches or greater than 12 inches from the ceiling”, and an alarm “should be installed at least 10 feet from a cooking appliance”, away from drafts. These are not separate deficiencies, but paint or tape on an alarm counts as obstructed.
Which smoke alarms qualify?
Federal law requires a “qualifying smoke alarm”. In a unit built before December 29, 2022 and not substantially rehabilitated since, that is a hardwired alarm or one that “uses 10-year non rechargeable, nonreplaceable primary batteries and is sealed, is tamper resistant, and contains silencing means”, and either kind must give hearing-loss notification as NFPA 72 requires. A unit built or substantially rehabilitated after that date needs hardwired alarms. An alarm that runs only on a replaceable 9-volt or AA battery does not qualify. The rule took effect December 29, 2024.
24 CFR 5.703 and the Smoke Alarm standard still say “battery-operated or hard-wired”, and HUD’s checklist has no line for alarm type. Notice PIH 2026-18 says NSPIRE “will be updated with the additional mandates soon”.
How does the inspector test smoke alarms?
The inspector presses each test button, watching whether the light “flashes, strobes, or changes pattern in any way” and listening for an alarm. With no test button, the inspector asks the owner or agent for a “smoke alarm maintenance certificate”. An alarm that keeps sounding after the test is cited, and so is one “covered by a foreign object (e.g., plastic bag, shower cap, zip tie, paint, tape).” Exposed wiring at a hardwired alarm is cited as an exposed conductor, also life-threatening.
Which units need a carbon monoxide alarm?
Federal law requires CO alarms or detectors installed to meet or exceed chapters 9 and 11 of the 2018 International Fire Code, and HUD calls its Carbon Monoxide Alarm standard “substantively consistent” with them. The standard requires an alarm when:
- The unit contains a fuel-burning appliance or fuel-burning fireplace.
- A bedroom, or a bathroom attached to it, contains a fuel-burning appliance or fireplace, or adjoins a space combustion gases can flow from.
- A forced-air furnace located elsewhere serves the unit or a bedroom.
- The building contains a fuel-burning appliance or fuel-burning fireplace.
- The unit or a bedroom is one story or less above or below an attached private garage with no natural ventilation, or enclosed with no ventilation system for vehicle exhaust.
HUD says “in most circumstances” only an appliance or fireplace in or directly attached to the unit, or an attached unventilated garage, triggers the rule, and such a garage calls for CO alarms even in an all-electric building.
Where do carbon monoxide alarms go?
In cases 1, 3 and 5, the alarm goes “in the immediate vicinity of each bedroom” or “within each bedroom”: inside or right outside each bedroom. In case 2, it goes inside each bedroom. With a furnace elsewhere, it may instead sit “within the room or area with the first duct register” if its signal goes automatically to an approved location. For an appliance elsewhere in the building with openings to the unit, it goes inside or right outside each bedroom, and the standard also allows an approved location between the appliance and the unit, or the ceiling of the appliance’s room. HUD’s standard does not define “immediate vicinity” or set a distance.
Where a person with a hearing impairment lives in the unit, HUD’s definition calls for “a distinct visual alarm or combination of audible and visual alarms”.
Combination alarms are judged under both the Smoke Alarm and Carbon Monoxide Alarm standards, and one that serves as a required smoke alarm must also meet the smoke alarm type rule.
How does the inspector test CO alarms?
The inspector presses a test button under 8 feet high and may ask you to press a higher one. Dead batteries fail, and every CO alarm present is tested, including one you did not have to install. A CO alarm with no test button is not cited under this test. A bag, shower cap, zip tie, paint, tape or decorative stickers over one count as obstructed.
HUD’s checklist items for smoke and CO alarms
These are the six alarm items on HUD’s checklist, each one on the life-threatening list:
HUD’s NSPIRE checklist for Housing Choice Voucher units, dated May 8, 2026, lists 6 deficiencies under the “Smoke Alarm” and “Carbon Monoxide” standards. Each quoted line is HUD’s own wording, with HUD’s severity, the time to fix it, and the areas of the checklist that list it.
Smoke Alarm
- “Smoke alarm is not installed where required.*” Life-threatening, fix within 24 hours · Unit, Inside
- “Smoke alarm is obstructed.” Life-threatening, fix within 24 hours · Unit, Inside
- “Smoke alarm does not produce an audio or visual alarm when tested.” Life-threatening, fix within 24 hours · Unit, Inside
Carbon Monoxide
- “Carbon monoxide alarm is missing, not installed, or not installed in a proper location.*” Life-threatening, fix within 24 hours · Unit
- “Carbon monoxide alarm is obstructed.” Life-threatening, fix within 24 hours · Unit, Inside
- “Carbon monoxide alarm does not produce an audio or visual alarm when tested.” Life-threatening, fix within 24 hours · Unit, Inside
*Affirmative Habitability Requirement per 24 CFR 5.703(d) and NSPIRE Final Rule
How to check your alarms room by room
- In an occupied unit, give your tenant any notice your lease and state law require.
- Note each fuel-burning appliance and fireplace in the unit and building, any forced-air furnace serving the unit from elsewhere, and any attached garage.
- In each bedroom, check for a smoke alarm. Where the unit needs CO alarms, check for one inside or right outside each bedroom (inside, in case 2).
- Walk from each bedroom door to the nearest smoke alarm outside it: 21 feet at most. If a door separates that alarm from the living area, check the living-area side too.
- Check for a smoke alarm on every other level, including the basement.
- Confirm each smoke alarm is hardwired, or sealed with a 10-year battery where that is allowed.
- Remove anything covering an alarm, and look for exposed wiring.
- Press every test button, fix any silent alarm, and have a smoke alarm maintenance certificate for any smoke alarm without a button.
- Check shared areas serving your unit for a smoke alarm on each level and in each common area.
If your tenant pulls a battery or covers an alarm, the 24-hour fix stays yours on housing assistance payments (HAP) contracts signed on or after June 6, 2024, or renewed after that date, unless your housing authority finds the household or a guest caused it beyond ordinary use and waives your duty. The family must then “take all steps permissible under the lease and State and local law” to get it fixed within 24 hours, and may lose its assistance. On contracts signed earlier and never renewed, the earlier rule applies: you are not responsible for a breach the family is responsible for, such as damage a household member or guest caused beyond ordinary wear and tear. A sealed alarm leaves no battery to pull.
Questions landlords ask
Do smoke detectors have to be hardwired for Section 8?
Under federal law, only in a unit built or substantially rehabilitated after December 29, 2022. In a unit built before that date and not substantially rehabilitated since, each smoke alarm may instead be sealed and tamper-resistant, with a hush feature and 10-year batteries that cannot be recharged or replaced, and either kind must give hearing-loss notification as NFPA 72 requires. Both rules have applied since December 29, 2024, under NSPIRE or HQS. An alarm that runs only on replaceable 9-volt or AA batteries meets neither. State or local law can require more.
Does a Section 8 unit need a smoke detector in every bedroom?
Yes. 24 CFR 5.703(d)(3) requires one inside each bedroom, and HUD’s September 30, 2025 notice says NSPIRE’s standards for installing smoke alarms “still apply” whichever standard your housing authority uses. The old HQS regulation required at least one on each level, including the basement, installed to NFPA 74 or its successor standards, and did not name bedrooms. Federal law now also requires one “in or near each sleeping area”.
Does every Section 8 unit need a carbon monoxide detector?
No. Under HUD’s Carbon Monoxide Alarm standard, a unit needs one when it has a fuel-burning appliance or fireplace, when a bedroom or its attached bathroom adjoins a space combustion gases can flow from, when a forced-air furnace located elsewhere serves it, or when it is one story or less above or below an attached private garage with no natural ventilation, or enclosed with no ventilation system for vehicle exhaust. HUD says a fuel-burning appliance elsewhere in the building calls for one only in limited circumstances, where the unit has openings to it. An attached, unventilated garage calls for one even in an all-electric building. State or local law can require more.
Do carbon monoxide detectors have to be hardwired?
HUD’s Carbon Monoxide Alarm standard does not set a power source, and HUD’s checklist has no item on power source. A CO alarm is cited if it is missing where required, obstructed, or silent when tested, including from dead batteries. The standard also says all requirements of sections 915 and 1103 of the International Fire Code must be met, though the inspector checks only its own criteria. Federal law’s hardwired or sealed 10-year battery rule covers smoke alarms, so it applies to a combination alarm that serves as a required smoke alarm. State or local law may set its own rule.
Who pays for smoke and carbon monoxide alarms in a Section 8 unit?
Carbon monoxide alarms are yours to pay for: Notice PIH 2022-01 says “For the HCV and PBV programs, the property owner or landlord is responsible for the cost of CO alarms or detectors.” Smoke alarms fall under your general duty in 24 CFR 982.404(a)(1): “The owner must maintain the unit in accordance with HQS.” Smoke alarms are part of HQS under either standard.
Sources
The 15 documents this guide relies on
- HUD NSPIRE HCV/PBV Inspection Checklist, version dated May 8, 2026 (OMB 2577-0289)
- NSPIRE Standard: Smoke Alarm, V3.0 (08/11/23)
- NSPIRE Standard: Carbon Monoxide Alarm, V3.0 (08/11/23)
- NSPIRE Standard: Electrical - Conductor, Outlet, and Switch, V3.0 (08/11/23)
- 24 CFR 5.703, National standards for the condition of HUD housing (eCFR)
- 24 CFR 982.404, Maintenance: owner and family responsibility; PHA remedies (eCFR)
- 42 U.S.C. 1437f(o)(21) and (o)(22), carbon monoxide alarms and qualifying smoke alarms (United States Code, 2024 edition, govinfo)
- Consolidated Appropriations Act, 2021 (Pub. L. 116-260), Division Q, Title I, Section 101, carbon monoxide alarms or detectors, govinfo copy
- Consolidated Appropriations Act, 2023 (Pub. L. 117-328), Division AA, Title VI, Section 601, smoke alarms, govinfo copy
- Notice PIH 2022-01, Carbon Monoxide Alarms or Detectors in HUD-Assisted Housing (Jan. 31, 2022), Wayback Machine copy
- HUD Notice PIH 2026-18, Implementation of NSPIRE Administrative Procedures for Voucher Programs (July 15, 2026), copy hosted by the Housing Authority of Gloucester County (NJ)
- 90 FR 46911 (Sept. 30, 2025), NSPIRE date extension for the HCV, PBV and Mod Rehab programs, govinfo copy
- NSPIRE Inspection Standards notice, 88 FR 40832 (June 22, 2023), govinfo copy
- 24 CFR 982.401(n), smoke detectors, as in effect before the NSPIRE rule (eCFR, May 10, 2023)
- 24 CFR 982.404 before the June 6, 2024 changes, for older contracts (eCFR, May 6, 2024)